5SL6106-7CC SIEMENS CIRCUIT BREAKER

February 26, 2019 0

SIEMENS

5SL6106-7CC

CIRCUIT BREAKER 230/400V 6KA, 1POLE, C, 6A

 

Description

 

Model
Product brand name SENTRON
Product designation Miniature circuit breakers
Design of the product 5SL miniature circuit breakers
 

General technical data

Number of poles 1
Number of poles / Note 1P
Tripping characteristic class C
circuit-breaker / Design 5SL6
Mechanical service life (switching cycles) / typical 20 000
Overvoltage category 3
 

Voltage

Type of voltage AC/DC
Insulation voltage
     ● with single-phase operation / with AC / Rated value 440 V
     ● with multi-phase operation / with AC / Rated value 440 V
 

Supply voltage

Supply voltage frequency / Rated value 50 HZ
 

Protection class

Protection class IP IP20, with connected conductors
Energy limiting class 3
 

Switching capacity

Switching capacity current
      ● acc. to EN 60898 / Rated value 6 KA
      ● acc. to IEC 60947-2 / Rated value 6KA
 

Dissipation

Active power loss

      ● for rated value of the current / with AC / in hot operating state / per pole 0.6 W
 

Electricity

rated current In / IEC, DIN/VDE / at 40 Cel 5.63602 A
Current / with AC / Rated value 6 A
 

Main circuit

Operating voltage
       ● minimum 24 V
       ● for DC / Rated value / maximum 60 V
       ● with single-phase operation / with AC /
maximum
250 V
       ● with multi-phase operation / with AC / maximum 440 V
 

Connections

Connectable conductor cross-section / stranded
        ● minimum 0.75  mm²
        ● maximum 35  mm²
Connectable conductor cross-section
        ● solid
               — minimum 0.75  mm²
               — maximum 35 mm²
        ● finely stranded / with core end processing
               — minimum 0.75 mm²
               — miximum 25 mm²
Tightening torque / with screw-type terminals
       ● minimum 2.5 N·m
       ● maximum 3 N·m
 

Mechanical Design

Height 90 mm
Width 18 mm
Depth 76 mm
mounting position any
Installation depth 70 mm
Number of width units 1
Net weight 115 g
 

Environmental conditions

Degree of pollution 2
Influence of the surrounding temperature Periodically +55°C, max. 95% humidity
Ambient temperature
       ● minimum -25°C
       ● maximum 40°C
       ● during storage / minimum -40°C
       ● during storage / maximum 75°C
 

Certificates

Equipment marking
       ● acc. to DIN EN 61346-2 F
       ● acc. to DIN EN 81346-2 F